Appendix e: boiler default settings, Benchmark 1.5ln dual-fuel low nox boiler, Gf-121 – AERCO BMK 1.5 LN Dual Fuel Feb 2013 User Manual

Page 121

background image

PR2: 05/01/11 Page

121 of 162

Benchmark 1.5LN Dual-Fuel Low NOx Boiler

Operation and Maintenance Manual

OMM-0041_0C

GF-121

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

APPENDIX E: BOILER DEFAULT SETTINGS

Table E-1: Boiler Default Settings

MENU & OPTION

FACTORY DEFAULT

Setup Menu

Password

0

Language

English

Unit of Temp

Fahrenheit

Comm Address

0

Baud Rate

9600

Configuration Menu

Internal Setpt

130°F

Unit Type

BMK Boiler Dual

Unit Size

1500 MBH

Fuel Type

Natural Gas

Boiler Mode

Constant Setpoint

Remote Signal

(If Mode = Remote Setpoint, Direct Drive or Combination)

4 – 20 mA / 1-5V

Bldg Ref Temp

(If Boiler Mode = Outdoor Reset)

70°F

Reset Ratio

(If Boiler Mode = Outdoor Reset)

1.2

Outdoor Sensor

Disabled

System Start Tmp

(If Outdoor Sensor = Enabled)

60°F

Setpt Lo Limit

60°F

Setpt Hi Limit

195°F

Temp Hi Limit

195°F

Max Valve Position

100%

Pump Delay Timer

0 min

Aux Start On Dly

0 sec

Failsafe Mode

Shutdown

Analog Output

Valve Position 0-10V

CAUTION: DO NOT Change

Lo Fire Timer

2 sec

Setpt Limit Band (If Setpt Limiting = Enabled)

5°F