CHAPTER 3: CONTROL PANEL OPERATION

Page

36 of 162 PR2: 05/09/12

Benchmark 1.5LN Dual-Fuel Low NOx Boiler

Operation and Maintenance Manual

OMM-0041_0C

GF-121

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

3.6 CONFIGURATION MENU

The Configuration Menu shown in Table 3-4 permits adjustment of the Internal Setpoint

(Setpt) temperature regardless of whether the valid password has been entered. Setpt is

required for operation in the Constant Setpoint mode. The remaining options in this menu

require the valid password to be entered, prior to changing existing entries. This menu

contains a number of other configuration settings which may or may not be displayed,

depending on the current operating mode setting.

NOTE

The Configuration Menu settings shown in Table 3-4 are

Factory-Set in accordance with the requirements

specified for each individual order. Therefore, under

normal operating conditions, no changes will be required.

Table 3-4: Configuration Menu

Available Choices or Limits

Menu Item Display

Minimum

Maximum

Default

Internal Setpt

Lo Temp Limit

Hi Temp Limit

130°F

Unit Type

Innovation, KC Boiler, KC Boiler LN,

BMK Boiler Std, BMK Boiler LN,

BMK Blr Std Dual, BMK Blr LN KC Water

Heater,

KC Wtr Heater LN,

Innovation WH

BMK Boiler Dual

Unit Size

500 MBH, 750 MBH, 800 MBH, 1000 MBH,

1060 MBH, 1500 MBH, 2000 MBH,

3000 MBH, 6000 MBH

1.5 MBTH

Fuel Type

Natural Gas, Propane

Natural Gas

Boiler Mode

Constant Setpoint, Remote Setpoint,

Direct Drive, Combination

Outdoor Reset

Constant Setpoint

Available Choices or Limits

Menu Item Display

Minimum

Maximum

Default

Remote Signal

(If Mode = Remote Setpoint, Direct

Drive or Combination)

4 – 20 mA/1 – 5V

0 -20 mA/0 – 5V

PWM Input (BMS)

Network

4 – 20 mA,

1-5V

Bldg Ref Temp (If Mode = Outdoor Reset)

40°F

230°F

70°F

Reset Ratio(If Mode = Outdoor Reset)

0.1

9.9

1.2

Outdoor Sensor

Enabled or Disabled

Disabled

System Start Tmp (If Outdoor Sensor-

Enabled)

30°F

100°F

60°F

Setpt Lo Limit

40°F

Setpt Hi Limit

60°F

Setpt Hi Limit

Setpt Lo Limit

195°F

195°F

Temp Hi Limit

40°F

210°F

195°F

Max Valve Position

40%

100%

100%

Pump Delay Timer

0 min.

30 min.

0 min.