beautypg.com

2 setting the unit, Benchmark 1.5ln dual-fuel low nox boiler, Gf-121 – AERCO BMK 1.5 LN Dual Fuel Feb 2013 User Manual

Page 13

background image

CHAPTER 2: INSTALLATION

PR2: 05/09/12 Page

13 of 162

Benchmark 1.5LN Dual-Fuel Low NOx Boiler

Operation and Maintenance Manual

OMM-0041_0C

GF-121

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

FOR MASSACHUSSETTS ONLY:

For Massachusetts installations, the boiler must be installed by a

plumber or gas fitter who is licensed within the Commonwealth of

Massachusetts. In addition, the installation must comply with all

requirements specified in Chapter 1 (Safety Precautions), pages

1-2 & 1-3.

Setting the Unit

2.4.2

The unit must be installed on a 4 inch to 6 inch housekeeping pad to ensure proper condensate

drainage. If anchoring the unit, refer to the dimensional drawings in Appendix F for anchor

locations. Two lifting tabs are provided at the top of the heat exchanger. Figure 2-2 shows the

location of the tab on the top-left side. The second tab is located on the top-right side of the heat

exchanger. USE THESE TWO TABS TO LIFT AND MOVE THE UNIT. Remove the top panel

from the unit to provide access to the lifting tabs. Remove the four (4) lag screws securing the

unit to the shipping skid. Lift the unit off the shipping skid and position it on the 4 inch to 6 inch

housekeeping concrete pad (required) in the desired location.

WARNING

WHEN LIFTING OR MOVING THE BOILER:

DO NOT MANIPULATE THE BOILER USING THE GAS

TRAIN OR BLOWER

WHEN USING THE LIFTING TABS, ENSURE THERE IS

NO LOAD PLACED ON THE GAS TRAIN OR BLOWER

Figure 2-2: Partial Top View Showing Lifting Tab Location