beautypg.com

1 constant setpoint mode, 2 indoor/outdoor reset mode, 3 boiler management system mode – AERCO BMK 1.5 LN Dual Fuel Feb 2013 User Manual

Page 20: Benchmark 1.5ln dual-fuel low nox boiler, Gf-121

background image

CHAPTER 2: INSTALLATION

Page

20 of 162 PR2: 05/09/12

Benchmark 1.5LN Dual-Fuel Low NOx Boiler

Operation and Maintenance Manual

OMM-0041_0C

GF-121

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

Figure 2-9: Input/Output (I/O) Box Location

Constant Setpoint Mode

2.9.1

The Constant Setpoint Mode is used when it is desired to have a fixed setpoint that does not

deviate. No wiring connections, other than AC electrical power connections, are required for

this mode. However, if desired, fault monitoring or enable/disable interlock wiring can be

utilized (see paragraphs 2.9.9.1 and 2.9.10).

Indoor/Outdoor Reset Mode

2.9.2

This mode of operation increases supply water temperature as outdoor temperatures decrease.

An outside air temperature sensor (AERCO Part No. 122790) is required. The sensor MUST

BE wired to the I/O Box wiring terminals (see Figure 2-10). Refer to paragraph 2.10.1 for

additional information on outside air temperature sensor installation.

Boiler Management System Mode

2.9.3

NOTE

BMS Model 168 can utilize either pulse width modulation (PWM)

or RS485 Modbus signaling to the Boiler. BMS II Model 5R5-384

and the AERCO Control System (ACS) can utilize only RS485

signaling to the Boiler.

When using an AERCO BMS, BMS II, or ACS (AERCO Control System), the field wiring is

connected between the BMS/BMS II/ACS Panel and each Boiler’s I/O Box terminal strip (Figure

2-10). Twisted shielded pair wire from 18 to 22 AWG must be utilized for the connections. The

BMS Mode can utilize either pulse width modulation (PWM) signaling, or RS485 Modbus

signaling. For PWM signaling, connections are made from the AERCO Boiler Management

System to the B.M.S. (PWM) IN terminals on the I/O Box terminal strip. For RS485 Modus

signaling, connections are made from the BMS/BMS II/ACS to the RS485 COMM terminals on

the I/O Box terminal strip. Polarity must be maintained and the shield must be connected only at

the AERCO BMS/BMS II/ACS. The boiler end of the shield must be left floating.
For additional instructions, refer to Chapter 5, paragraph 5.6 in this manual. Also, refer to GF-