2 reset i/o fault, Reset i/o fault – Pilz PNOZ s50 C User Manual
Page 55

Operation
Operating Manual PNOZ s50
1002194EN02
55
Place
Value
Terminal
Designation of the input/output state
1
O3
Output for fault signal
2
T0
Output for test pulse 0
4
T1
Output for test pulse 1
8
Reserved
5
0
No error
1
O1+
Output of power circuit 1 (High Side)
2
O1
Output of power circuit 1 (Low Side)
4
O4
Output of status for power circuit 1
8
Reserved
6
0
No error
1
O2+
Output of power circuit 2 (High Side)
2
O2
Output of power circuit 2 (Low Side)
4
O5
Output of status for power circuit 2
8
Reserved
7
0
Reserved
7.2
Reset I/O Fault
The device switches to the "I/O Fault" state if a fault has been detected at the inputs or out
puts. Once it has been rectified, the fault must be reset.
There are three options for resetting an "I/O Fault" and restarting the device.
Option one: Switch supply voltage A1/A2 off and then on again
1. Switch off the device's supply voltage (terminals A1 and A2)
2. Switch the device's supply voltage back on.
The device restarts.
Option two: Display menu reboot
1. Select Reboot in menu level 3.
2. Select Yes and press the rotary knob.
The device restarts.
Option three: Switch inputs Y10/Y11 or Y20/Y22
This option should be considered if you wish to reset the fault from the higher level control
system.
Using one power circuit:
}
The fault is reset by a 1/0 pulse edge at one of the inputs Y10/Y11 or Y20/Y21.
}
A 0/1 pulse edge switches on the corresponding power circuit.