Commissioning

Operating Manual PNOZ s50
1002194­EN­02

26

6

Commissioning

6.1

Wiring

6.1.1

General wiring guidelines

Note:

}

Information given in the "Technical details" must be followed.

}

Use copper wire that can withstand 75 °C.

}

The wiring must be designed to achieve sufficient noise immunity and protection
against noise emissions in terms of EMC. Please also refer to DIN EN 60204­1 (Elec­
trical equipment of machines).

Inputs

}

Appropriate wiring must be used to exclude short circuits between the inputs or to a
supply line!

Outputs

}

If short circuits occur between the cable from the output to the load and a supply line, it
will no longer be possible to switch off the load.

Possible remedy: Exclude the error by using separate multicore cable for supply
voltages

}

Use appropriate wiring to exclude short circuits between the outputs!

6.1.2

Pin assignment

Female connector X1

Terminal

Description

A2 A2 S36 S35 S11 S11 T1 T0

x

1

A2

Reference potential for

­ Device's supply voltage

­ Inputs

­ Fault signal and status outputs

S36

Standard input for slow shutdown, power
circuit 2

S35

Standard input for slow shutdown, power
circuit 1

S11

Voltage output 24 VDC

S11

Voltage output 24 VDC

T1

Test pulse output 1

T0

Test pulse output 0