Pilz PNOZ s50 C User Manual
Page 45

Commissioning
Operating Manual PNOZ s50
1002194EN02
45
Overview
Display format
Description
Input Voltage
Configure the sup
ply voltage to the
power circuits
Input Voltage
B1/B2
U 24 V
Cancel Store
U < 24 > V Select supply voltage for
power circuit, values: 24, 48 V
Cancel – Exit menu without confirming the
entry
Store – Confirm entry
Configure feedback loops Y1 and Y2
Feedback
Configure feedback
loops
Feedback
Pulsing
Y1
Y2
Pulsing – Configure test pulses
Y1 – Switch to the Y1 menu to configure
feedback loop Y1
Y2 Switch to the Y2 menu to configure
feedback loop Y2
Y1/Y2 Pulse
Activate test pulse
Y1/Y2 Pulse
Pulse On/Off
Cancel Store
Pulse On: Test pulse on
Pulse Off: Test pulse off
Cancel – Exit menu without confirming the
entry
Store – Confirm entry
Please note: The test pulses can only be
activated simultaneously for both feedback
loops Y1 and Y2.
Y1 or Y2
Switch to sub
menus for configur
ation of the feed
back loops
Y1
Logic
Timing
Y2
Logic – Switch to Logic Y1 or Logic Y2
menu
Timing Switch to Timing Y1 or Timing
Y2 menu
Y1 Logic or Y2 Lo
gic
Define N/C or N/O
contact in the feed
back loop
Y1 Logic
Logic N/O / N/C
Cancel Store
Y2 Logic
Logic < N/O /N/C> Input logic for feed
back loop Y1 or Y2:
N/O: N/O contact
N/C: N/C contact
Cancel – Exit menu without confirming the
entry
Store – Confirm entry
Y1 Timing or Y2
Timing
Y1 Timing
Ton
Toff
Y2 Timing
Ton – Switch to submenu for configuration
of the max. ventilation time
Toff – Switch to submenu for configuration
of the max. application time