Commissioning

Operating Manual PNOZ s50
1002194­EN­02

45

Overview

Display format

Description

Input Voltage

Configure the sup­
ply voltage to the
power circuits

Input Voltage
B1/B2
U 24 V
Cancel Store

U < 24 > V ­ Select supply voltage for
power circuit, values: 24, 48 V

Cancel – Exit menu without confirming the
entry

Store – Confirm entry

Configure feedback loops Y1 and Y2

Feedback

Configure feedback
loops

Feedback

Pulsing

Y1

Y2

Pulsing – Configure test pulses

Y1 – Switch to the Y1 menu to configure
feedback loop Y1

Y2 ­ Switch to the Y2 menu to configure
feedback loop Y2

Y1/Y2 Pulse

Activate test pulse

Y1/Y2 Pulse

Pulse On/Off

Cancel Store

Pulse On: Test pulse on

Pulse Off: Test pulse off

Cancel – Exit menu without confirming the
entry

Store – Confirm entry

Please note: The test pulses can only be
activated simultaneously for both feedback
loops Y1 and Y2.

Y1 or Y2

Switch to sub­
menus for configur­
ation of the feed­
back loops

Y1

Logic

Timing

Y2

Logic – Switch to Logic Y1 or Logic Y2
menu

Timing ­ Switch to Timing Y1 or Timing
Y2
 menu

Y1 Logic or Y2 Lo­
gic

Define N/C or N/O
contact in the feed­
back loop

Y1 Logic
Logic N/O / N/C

Cancel Store

Y2 Logic

Logic < N/O /N/C> ­ Input logic for feed­
back loop Y1 or Y2:

N/O: N/O contact

N/C: N/C contact

Cancel – Exit menu without confirming the
entry

Store – Confirm entry

Y1 Timing or Y2
Timing

Y1 Timing

Ton

Toff

Y2 Timing

Ton – Switch to submenu for configuration
of the max. ventilation time

Toff – Switch to submenu for configuration
of the max. application time