Pilz PNOZ s50 C User Manual
Page 51

Operation
Operating Manual PNOZ s50
1002194EN02
51
Cat.
No.
Error message
Description
Remedy
7
1
Reinit Memory
The device memory has been
reinitialised. All parameters have
been set to the default settings.
Purely for information
20
0
Short Circuit
Short circuit at power circuit
O1+/O1 or O2+/O2
Parameter 1:
0x00100000: O1+
0x00200000: O1
0x01000000: O2+
0x02000000: O2
Ensure that the power circuit is
wired correctly
Rectify short circuit
20
1
Readback fail
Output voltage of power circuit
O1+/O1 or O2+/O2 does not
correspond to the configured
output voltage.
Parameter 1:
0x00100000: O1+
0x00200000: O1
0x01000000: O2+
0x02000000: O2
Ensure that the power circuit is
wired correctly
Rectify short circuits or shorts
between contacts
20
2
Open Circuit
Open circuit at power circuit
O1+/O1 or O2+/O2. Current is
too low in the on state.
Parameter 1
0x00100000: O1+
0x00200000: O1
0x01000000: O2+
0x02000000: O2
Ensure that the power circuit is
wired correctly
Rectify open circuit
20
3
Test fail
Error during off test of power cir
cuits O1+/O1 or O2+/O2.
Parameter 1
0x00100000: O1+
0x00200000: O1
0x01000000: O2+
0x02000000: O2
Ensure that the power circuit is
wired correctly
Rectify short circuits or shorts
between contacts
20
4
Test fail
Error during on test of power cir
cuits O1+/O1 or O2+/O2.
Parameter 1
0x00100000: O1+
0x00200000: O1
0x01000000: O2+
0x02000000: O2
Ensure that the power circuit is
wired correctly