beautypg.com

Pilz PNOZ s50 C User Manual

Page 51

background image

Operation

Operating Manual PNOZ s50
1002194­EN­02

51

Cat.

No.

Error message

Description

Remedy

7

1

Reinit Memory

The device memory has been
reinitialised. All parameters have
been set to the default settings.

Purely for information

20

0

Short Circuit

Short circuit at power circuit
O1+/O1­ or O2+/O2­

Parameter 1:

0x00100000: O1+

0x00200000: O1­

0x01000000: O2+

0x02000000: O2­

­Ensure that the power circuit is
wired correctly

­ Rectify short circuit

20

1

Readback fail

Output voltage of power circuit
O1+/O1­ or O2+/O2 does not
correspond to the configured
output voltage.

Parameter 1:

0x00100000: O1+

0x00200000: O1­

0x01000000: O2+

0x02000000: O2­

­Ensure that the power circuit is
wired correctly

­ Rectify short circuits or shorts
between contacts

20

2

Open Circuit

Open circuit at power circuit
O1+/O1­ or O2+/O2­. Current is
too low in the on state.

Parameter 1

0x00100000: O1+

0x00200000: O1­

0x01000000: O2+

0x02000000: O2­

­Ensure that the power circuit is
wired correctly

­ Rectify open circuit

20

3

Test fail

Error during off test of power cir­
cuits O1+/O1­ or O2+/O2­.

Parameter 1

0x00100000: O1+

0x00200000: O1­

0x01000000: O2+

0x02000000: O2­

­Ensure that the power circuit is
wired correctly

­ Rectify short circuits or shorts
between contacts

20

4

Test fail

Error during on test of power cir­
cuits O1+/O1­ or O2+/O2­.

Parameter 1

0x00100000: O1+

0x00200000: O1­

0x01000000: O2+

0x02000000: O2­

Ensure that the power circuit is
wired correctly