beautypg.com

Pilz PNOZ s50 C User Manual

Page 17

background image

Function description

Operating Manual PNOZ s50
1002194­EN­02

17

INFORMATION

Please note that when using slow shutdown, the inputs for fast shutdown
(Y10/Y11 and Y20/21) must have a "1" signal.

Power circuit 1

S35

O1+, O1­

1/0 pulse edge

Switches off power circuit 1

Power circuit 2

S36

O2+, O2­

1/0 pulse edge

Switches off power circuit 2

INFORMATION

Please note: Input S35 switches output O1+/O1­; input S36 switches output
O2+/O2­. In the event of a fault, however, both outputs will switch off.

INFORMATION

If slow shutdown is not being used, 24 VDC must be permanently applied to
terminals S35 and S36 (see section entitled "Conditions for fast and slow
shutdown").