Pilz PNOZ s50 C User Manual

Page 15

background image

Function description

Operating Manual PNOZ s50
1002194­EN­02

15

INFORMATION

At the safe inputs Y10 and Y11 / Y20 and Y21, a "0" signal must be present
before the corresponding output O1+/O1­ / O2+/O2­ can be switched by a
"1" signal at both inputs. If this is not the case, a fault is signalled and the
LED "Out 1" or "Out 2" flashes (the diagram below illustrates this, using the
dual­pole input Y10/Y11 and the output O1+/O1­ as an example).

O3

Fig.: Start­up condition for inputs Y10/Y11

INFORMATION

Please note: Inputs Y10/Y11 switch output O1+/O1­; inputs Y20/Y21 switch
output O2+/O2­. In the event of a fault, however, both outputs will switch off.
Status outputs O4/O5 also switch off, irrespective of the switch status of the
inductive load. At the time an input, e.g. Y11, is switched on, if the other in­
put, e.g. Y10, is not at "0", the fault signal output O3 will signal a fault via a
"0" signal.

After the output O1+/O1­ and/or O2+/O2­ is switched on, the voltage U

B1B2

 is available for a

configurable overexcitation time U

over

. Once the overexcitation time t

over

 has elapsed, the

voltage is reduced through pulse width modulation (PWM). The overexcitation time t

over

 and

the reduced voltage U

Avg

 are configured via the display.

INFORMATION

The overexcitation time t

over

 can also be switched off for each power circuit.

In this case, the output voltage of the power circuits O1+/O1­ and/or O2+/
O2­ equals the supply voltage U

B1B2

.