Operation

Operating Manual PNOZ s50
1002194­EN­02

53

Cat.

No.

Error message

Description

Remedy

23

1

Feedback Err

State of the feedback loop is not
as expected after the power cir­
cuits are switched on

Parameter 1:

0x00000080: Y1

0x00000800: Y2

­ Ensure that the feedback loops
are wired correctly

­ Ensure that the feedback loops
are configured correctly

­ Ensure that the load is applied

23

2

Feedback Ton

State of the feedback loop is not
as expected after the ventilation
time has elapsed

Parameter 1:

0x00000080: Y1

0x00000800: Y2

Parameter 2 (type of testing):

0x00000001: As ventilation time
elapses

0x00000002: After ventilation
time has elapsed

­ Ensure that the feedback loops
are wired correctly

­ Ensure that the feedback loops
are configured correctly

­ Ensure that the load is applied

­ Ensure that the ventilation time is
configured correctly

23

3

Feedback Toff

State of the feedback loop is not
as expected after the application
time has elapsed

Parameter 1:

0x00000080: Y1

0x00000800: Y2

Parameter 2 (type of application
time):

0x00000001: Toff fast shutdown

0x00000002: Toff slow shutdown

0x00000003: Toff fast shutdown
before ventilation time has
elapsed

0x00000004: Slow shutdown be­
fore ventilation time has elapsed

0x00000005: Fast shutdown
after ventilation time for slow
shutdown has elapsed

­ Ensure that the feedback loops
are wired correctly

­ Ensure that the feedback loops
are configured correctly

­ Ensure that the load is applied

­ Ensure that the application time
is configured correctly

24

0

Defect Card

Cannot read chip card.

­ Check chip card

­ Insert a valid chip card into the
card slot

26

0

Supply Error

After switching on O1+/O1­ or
O2+/O2­, the supply voltage to
the power circuits B1/B2 is out­
side the permitted range

Parameter 1:

0x00000002: B1/B2

Check the supply voltage