Publication IASIMP-QS011B-EN-P — January 2009
Appendix C
Troubleshooting
4. If this is not the problem, move to rung 9 of the R03_Commands_AUTO routine and carefully
note what value is in the AutoCycle.StepIndex register as you press the green reset button
again on the HMI.
5. Use the table below to determine where the cycle is stopping and what action to take next.
Correct Aborted/Resetting State Problem: Reset Command Is Not Commanding Any Action
The reset command is not commanding any action. Perform the following steps to correct this
condition.
1. Observe the logic on rung 1 of the R03_Commands_AUTO routine.
2. Verify that the start request is coming from the HMI.
3. If not, make sure that your controller is in Run Mode and the HMI is communicating properly
with the controller.
If AutoCycle.StepIndex =
The current state is:
Take this action:
0
Stopped
Go to
Correct Aborted/Resetting State Problem: Reset Command Is Not
Commanding Any Action
10
Resetting
Go to
Correct Aborted/Resetting State Problem: AutoCycle.StepIndex Stops at 10
20
Resetting
Go to
Correct Aborted/Resetting State Problem: AutoCycle.StepIndex Stops at 20