Rockwell Automation 9307 FactoryTalk EnergyMetrix User Manual
Page 171

7
•
RT (Real Time)
171
Demand/IO Tab
This displays and sets demand parameters, output control parameters and status input
counter input scaling factors for an Allen-Bradley PowerMonitor 5000 unit.
Period length (minutes)
Enter the length of the demand period:
1…99. The power monitor internal clock measures the period for both the actual
and the projected demand values.
0. Disables projected demand. If Demand source is set to 0, internal time, disables
demand calculation.
Number of periods
Enter 1…15 to set the number of demand periods to be averaged.
Demand source
Selects the source of the demand period timing.
Forced demand sync. delay (seconds)
Defines how long the power monitor waits for an external end of interval signal before
it starts a new demand period.
Relay outputs
Select the following parameters for each of the relay outputs KYZ relay, Relay 1, 2
and 3:
Control source
Selects which parameter is used to control the relay output.
Output scale
For energy pulse operation, defines how many increments of the Metering
Parameter occur to pulsed or toggle the output. Range: 1…100,000.
Pulse width (mS)
Sets the duration of the output pulse (in milliseconds). Range: 50 to 1000, or zero
for KYZ-style toggle output.
Default state on comm loss
Defines the behavior of outputs in the event a Class 1 Exclusive Owner
connection is lost.
Status input scale
Defines the scaling factor applied to the status input S1 thru S4 counters. Range:
1…1,000,000.