1797-oe8h calibration item byte channel-mask -19, 1797-oe8h calibration item byte channel-mask – Rockwell Automation 1797-OE8H FLEX Ex HART Analog Modules User Manual User Manual
Page 95
Publication 1797-6.5.3 - March 2006
Calibrate Your Module 5-19
1797-OE8H Calibration Item Byte Channel-Mask
The Calibration item byte channel-mask uses each bit of the byte to
correspond to one channel: where 1 is calibrate this channel and 0 is do not
calibrate this channel. The LSB corresponds to channel 0, for example, 0x03 >
channel 0 and 1 have to be calibrated. Only one channel can be calibrated at a
time. If there are more channels selected within the calibration commands, the
I/O module signals an error.
Table 5.14 1797-OE8HCalibration Item Byte Value Identifier List
Identifier (Decimal)
Value
Access Rule
0
Offset channel 0
Read/write
…
…
7
Offset channel 7
8
Gain channel 0
…
…
15
Gain channel 7
16
Offset current-read-back
channel 0
…
…
23
Offset current-read-back
channel 7
24
Gain current-read-back
channel 0
…
…
31
Gain current-read-back
channel 7
32
Offset voltage-read-back
channel 0
…
…
39
Offset voltage-read-back
channel 7
7
6
5
4
3
2
1
0
Calibrate channel 0
:
Calibrate channel 1
Calibrate channel 7