B-14 FLEX Ex HART Module Commands
Command 139
The Reset Transmitter Cumulative Responses command returns the OR
combination of communication errors and status response bits. No more than
35 instruments may be requested.
8
STATUS_0
OR of status byte in instrument 0 replies
—
…
EXT_ADDR_i
Extended address of instrument i
…
COUNT_i
Bytes before next item
…
ERROR_i
Error i
…
COMM_ERR_i
OR of communication error in instrument i
replies
…
STATUS_i
OR of status byte in instrument i replies
…
…
…
Command-specific Response Codes
5
Error
Too few data bytes received
16
Error
Access restricted
17
Error
Too many items requested
32
Error Busy
Table B.14 Command 139 Request and Response Data Bytes
Byte
Description
Value
Request Data Bytes
0…4
EXT_ADDR_0
Extended address of instrument 0
—
5
COUNT_0
Bytes before next item
…
EXT_ADDR_i
Extended address of instrument i
…
COUNT_i
Bytes before next item
…
…
…
Response Data Bytes
0…4
EXT_ADDR_0
Extended address of instrument 0
—
5
COUNT_0
Bytes before next item
6
ERROR_0
Error 0
0 = No error.
64 = Unknown
instrument. No
data is included
for that
instrument.
…
EXT_ADDR_i
Extended address of instrument i
—
Table B.13 Command 138 Request and Response Data Bytes
Byte
Description
Value