Command 141 – Rockwell Automation 1797-OE8H FLEX Ex HART Analog Modules User Manual User Manual
Page 140

Publication 1797-6.5.3 - March 2006
B-16 FLEX Ex HART Module Commands
Command 141
The Delete the Number of Command Requests and Errors of the
Transmitters command resets the communication statistic. No more than 35
instruments may be requested.
…
COUNT_i
Bytes before next item
—
…
ERROR_i
Error i
…
TRIES_i
Number of commands sent to instrument i
by IOM-HART
…
FAILS_i
Number of commands that failed with
instrument i (no reply or communication
error)
…
…
…
Command-specific Response Codes
5
Error
Too few data bytes received
16
Error
Access restricted
17
Error
Too many items requested
32
Error Busy
Table B.16 Command 141 Request and Response Data Bytes
Byte
Description
Value
Request Data Bytes
0…4
EXT_ADDR_0
Extended address of instrument 0
—
5
COUNT_0
Bytes before next item
…
EXT_ADDR_i
Extended address of instrument i
…
COUNT_i
Bytes before next item
…
…
…
Response Data Bytes
0…4
EXT_ADDR_0
Extended address of instrument 0
—
5
COUNT_0
Bytes before next item
6
ERROR_0
Error 0
0 = No error.
64 = Unknown
instrument.
…
EXT_ADDR_i
Extended address of instrument i
—
…
COUNT_i
Bytes before next item
…
ERROR_i
Error i
…
…
…
Table B.15 Command 140 Request and Response Data Bytes
Byte
Description
Value