Command 135 – Rockwell Automation 1797-OE8H FLEX Ex HART Analog Modules User Manual User Manual

Page 134

background image

Publication 1797-6.5.3 - March 2006

B-10 FLEX Ex HART Module Commands

Command 135

For the given long frame addresses, the Read Dynamic Data of the
Transmitters command returns the following transmitter data:

• Selected SCAN command
• Long frame address
• HART data

No more than seven instruments may be requested.

Table B.10 Command 135 Request and Response Data Bytes

Byte

Description

Value

Request Data Bytes

0…4

EXT_ADDR_0

Extended address of instrument 0

5

COUNT_0

Bytes before next item

EXT_ADDR_I

Extended address of instrument I

COUNT_I

Bytes before next item

Response Data Bytes

0

SCAN_CMD

Scan command used

1 = Command 1
2 = Command 2
3 = Command 3

1…5

EXT_ADDR_0

Extended address of instrument 0

6

COUNT_0

Bytes before next item

7

ERROR_0

Error 0

0 = No error.
64 = The
requested
instrument is not
on the scan list.
No data is
included for that
instrument.

8

DATA_0

Reply from the instrument 0 (status bytes +
data bytes)

EXT_ADDR_I

Extended address of instrument I

COUNT_I

Bytes before next item

ERROR_i

Error i

DATA_i

Reply from the I-th instrument (status
bytes + data bytes)