B-10 FLEX Ex HART Module Commands
Command 135
For the given long frame addresses, the Read Dynamic Data of the
Transmitters command returns the following transmitter data:
• Selected SCAN command
• Long frame address
• HART data
No more than seven instruments may be requested.
Table B.10 Command 135 Request and Response Data Bytes
Byte
Description
Value
Request Data Bytes
0…4
EXT_ADDR_0
Extended address of instrument 0
—
5
COUNT_0
Bytes before next item
…
EXT_ADDR_I
Extended address of instrument I
…
COUNT_I
Bytes before next item
…
…
…
Response Data Bytes
0
SCAN_CMD
Scan command used
1 = Command 1
2 = Command 2
3 = Command 3
1…5
EXT_ADDR_0
Extended address of instrument 0
—
6
COUNT_0
Bytes before next item
7
ERROR_0
Error 0
0 = No error.
64 = The
requested
instrument is not
on the scan list.
No data is
included for that
instrument.
8
DATA_0
Reply from the instrument 0 (status bytes +
data bytes)
—
…
EXT_ADDR_I
Extended address of instrument I
…
COUNT_I
Bytes before next item
…
ERROR_i
Error i
…
DATA_i
Reply from the I-th instrument (status
bytes + data bytes)