Understand Configurable FLEX Ex Analog Module Features 2-19
1797-IE8H and -OE8H
Extended Configuration
Data Table
The FLEX Ex HART modules are addressed by using an MSG or CIO
instruction. When using one of these instructions, configure it to the
following:
• Class: 0x7D
• Instance:
Slot number (range from 1 to 8 with 1 being the I/O
module closest to the adapter
• Attribute: 0x66
• Service: 0x0E for a get attribute single or 0x10 for a set attribute single
Also, configure the communication path to the target I/O module.
For a set attribute single, configure two words as defined in the Extended
Configuration Data Table to be sent to the I/O module.
For a get attribute single, two words configured as defined in the Extended
Configuration Data Table will be returned from the instruction.
Table 2.17 1797-IE8H and -OE8H Extended Configuration Data Table
Bit
→
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Word
↓
0
PMI
ch 7
PMI
ch 6
PMI
ch 5
PMI
ch 4
PMI
ch 3
PMI
ch 2
PMI
ch 1
PMI
ch 0
SME
ch 7
SME
ch 6
SME
ch 5
SME
ch 4
SME
ch 3
SME
ch 2
SME
ch 1
SME
ch 0
1
Reserved
HART Read Back Threshold
ch 4…7
HS
LED
HS
Inht
50/
60 Hz
HART Read Back Threshold
ch 0…3
Where:
ch = channel
PMI = Primary Master Inhibit
SME = Secondary Master Enable
HS LED = HART Status LEDs
HS Inht = HART Status Inhibit