Publication 1797-6.5.3 - March 2006

Troubleshoot the FLEX Ex Analog I/O Modules 7-3

Repair

This module is not field repairable. Any attempt to open this module will void
the warranty and IS certification. If repair is necessary, return this module to
the factory.

Chapter Summary

In this chapter you learned how to troubleshoot the FLEX Ex analog I/O
modules. Move to Appendix A to see the specifications for your module.

Table 7.2 1797-OE8H Status Indicators

Indicator

Color

State

Meaning

Status

Red

On

At power cycle – Channel 0 indicator lights when you
cycle power until all internal diagnostics are checked.
After successful power cycle, the indicator goes off if no
fault is present.

After successful powerup – Indicates a critical fault (for
example, diagnostic failure)

Blinking (when
faults are
enabled, and bit
set)

Indicates a noncritical channel fault

Yellow

On/blinking

HART device was found on the associated channel (when
configured)

Power

Off

Module not powered

Green

On

Module receiving power

Blinking

No flexbus communication