Command 136
For the given long frame addresses, the Read SCAN Status for the
Transmitters command sets the SCAN status of the transmitters (0 = disable
SCAN, 1 = enable SCAN). No more than 31 instruments may be requested.
Command-specific Response Codes
5
Error
Too few data bytes received
16
Error
Access restricted
17
Error
Too many items requested
32
Error Busy
Table B.11 Command 136 Request and Response Bytes
Byte
Description
Value
Request Data Bytes
0…4
EXT_ADDR_0
Extended address of instrument 0
—
5
COUNT_0
Bytes before next item
…
EXT_ADDR_I
Extended address of instrument I
…
COUNT_I
Bytes before next item
…
…
…
Response Data Bytes
0…4
EXT_ADDR_0
Extended address of instrument 0
—
5
COUNT_0
Bytes before next item
6
ERROR_0
Error 0
0 = No error.
64 = Unknown
instrument. No
data is included
for that
instrument.
7
SCAN_0
Instrument 0 scan status
0 = Instrument is
not scanned.
1 = Instrument is
scanned.
…
EXT_ADDR_I
Extended address of instrument I
—
…
COUNT_I
Bytes before next item
…
ERROR_I
Error I
…
SCAN_I
Instrument I scan status
Table B.10 Command 135 Request and Response Data Bytes
Byte
Description
Value