Rockwell Automation 1797-OE8H FLEX Ex HART Analog Modules User Manual User Manual
Page 93
Publication 1797-6.5.3 - March 2006
Calibrate Your Module 5-17
Table 5.12 1797-OE8H Interpretation of Calibration Data Structure Content During Read Access (Error Status)
Command Byte
Item Byte
Data1 Byte
Data2 Byte
Status (Binary)
Command Bits 0…5 (Decimal)
01
Error
3
The written min scale value of Current was not
accepted/internal read back erroneous
Channel-Mask
Value
low-byte
Value
high-byte
4
The written min scale value of Voltage was not
accepted/internal read back erroneous
5
The written max scale value of Current was not
accepted/internal read back erroneous
6
The written max scale value of Voltage was not
accepted/internal read back erroneous
7
Reserved
(1)
Reserved
Reserved
Reserved
8
The calibration values are not set to default
0
0
0
9
The specified calibration value is not set to default Value-identifier
10
The specified calibration value is not written
Value
low-byte
Value
high-byte
11
Reserved
(2)
Reserved
Reserved
Reserved
12
Reserved
13
Reserved
14
Reserved
15…61 Unknown command is mirrored back
0
0
0
62
The specified setup value is not written
(3)
Setup
value-identifier
Value
low-byte
Value
high-byte
63
The setup data could not be saved to EEPROM
0
0
0
(1)
Do not use. Designated for future use.
(2)
Reserved. Used during manufacture of the product. Do not use.
(3)
Only for internal use. Do not use for calibration purposes.