B-24 FLEX Ex HART Module Commands
Command 159
With the Write Special Loop SCAN Parameters command, the threshold data
length (0 to 62) and the SCAN command to be used can be written for the
given current loop and polling addresses (must be 0).
Command 164
With the Cached Data Reply CMD 0, 13, 16 command, results of command 0,
13, and 16 are combined in a response protocol.
Table B.27 Command 159 Request and Response Data Bytes
Byte
Description
Value
Request Data Bytes
0
CH_NUM
Channel number
0…7
1
SHORT_ADDR
Short address used for this channel
0…15
2
THRESH
Threshold data length for special scan
0…62
3
SCAN_CMD
Scan command to be used
—
Response Data Bytes
0
CH_NUM
Channel number
0…7
1
SHORT_ADDR
Short address used for this channel
0…15
2
THRESH
Threshold data length for special scan
0…62
3
SCAN_CMD
Scan command being used
—
4…8
EXT_ADDR
Extended address of instrument at address
SHORT_ADDR
Command-specific Response Codes
2
Error
Invalid selection
5
Error
Too few data bytes received
9
Error
First parameter too large (SHORT_ADDR out of range)
11
Error
Second parameter too large (THRESH out of range)
16
Error
Access restricted
32
Error Busy
64
Error
Unknown (no instrument at specified SHORT_ADDR)