beautypg.com

Command 131 – Rockwell Automation 1797-OE8H FLEX Ex HART Analog Modules User Manual User Manual

Page 131

background image

Publication 1797-6.5.3 - March 2006

FLEX Ex HART Module Commands B-7

Command 131

For the given long frame addresses, the Read Static Data of Transmitters
command returns the following transmitter data:

• Current loop number, 0 to 15
• Polling address
• Supported HART revision
• Minimum count of required preambles, 5 to 20

There are no request data bytes.

Table B.6 Command 131 Response Data Bytes

Byte

Description

Value

Response Data Bytes

0…4

EXT_ADDR_0

Extended address of instrument 0

5

ERROR_0

Error 0

0 = Instrument
present. Data for
that instrument is
included in reply.
64 = Unknown
instrument. Data
for that
instrument is not
included in reply.

EXT_ADDR_I

Extended address I

ERRO_I

Error I

Command-specific Response Codes

16

Error

Access restricted

32

Error

Busy

This manual is related to the following products: