beautypg.com

Loop functionality verification – Rockwell Automation 1797-OE8H FLEX Ex HART Analog Modules User Manual User Manual

Page 102

background image

Publication 1797-6.5.3 - March 2006

6-4 Apply FLEX Ex Analog I/O Modules

1797-IE8H Functional and IS Parameters

The figure below provides data, on the Flex Ex analog input modules, which
can be matched to this transmitter.

Loop Functionality Verification

The functional characteristics will be checked first. The figure below shows the
general situation which must be analyzed for proper loop function.

On the left are the module components of the voltage source to run the loop
and its internal source resistance. In the center is the cable. It represents a loss
with regard to its resistance. Cable resistance is a function of cable length. On
the right is the transmitter, which has a minimum voltage it must see to
function properly.

I

Analog Input

V>23V at I = 0 mA

V>17V at I = 22 mA

0…22 mA Measurement Range

EEx ia/ib IIB/IIC T4

Uo<24.4V

Io<92.5 mA

Flexbus

Ca = 119 nF

La = 4 mH

P

+

-V

sig

+V

4 to 20 mA

Xmit

273

23.7V

10

Bus

uC

HART
modem

Ci<10 pF/m

Li<0.5 uH/m

R<0.1

Ω/m

Ca = 118 nF

La = 4 mH

Transmitter

Minimum

Voltage = 14V

+

Cable resistance loss

+

Module source voltage = 17V

Module source resistance = 273

+

sig

10

Module sense resistance

= 10

273

17V

This manual is related to the following products: