Input, Diagnostic status data hart rebuild bit, Fault alarm – Rockwell Automation 1797-OE8H FLEX Ex HART Analog Modules User Manual User Manual
Page 172
Publication 1797-6.5.3 - March 2006
D-8 Configure the 1797-OE8H Module in RSLogix 5000 Software Over the ControlNet Network
Input
Refer to the following tables for input information.
Diagnostic Status Data
HART Rebuild Bit
The HART rebuild bit is [Adapter Name]:[Slot].I.Data[0].7.
Fault Alarm
Bit 3
Bit 2
Bit 1
Bit 0
Normal
0
0
0
0
Calibration Failure
0
0
0
1
Configuration Failure
0
0
1
0
Message Failure
0
0
1
1
Lead Break Detection
0
1
0
0
EEPROM Failure
0
1
0
1
RAM Failure
0
1
0
1
ROM Failure
0
1
1
1
Calculation Failure
1
0
0
0
Data Out of Range
1
0
1
1
Channel
Bits
0
[Adapter Name]:[Slot]:I.Data[0].8
1
[Adapter Name]:[Slot]:I.Data[0].9
2
[Adapter Name]:[Slot]:I.Data[0].10
3
[Adapter Name]:[Slot]:I.Data[0].11
4
[Adapter Name]:[Slot]:I.Data[0].12
5
[Adapter Name]:[Slot]:I.Data[0].13
6
[Adapter Name]:[Slot]:I.Data[0].14
7
[Adapter Name]:[Slot]:I.Data[0].15