FLEX Ex HART Module Commands B-21
Command 149
Command 149 is the Write SCAN Status command.
Command 152
The Read Loop Search Type command determines the polling address used to
search for a device that has not responded after multiple requests
(disappeared). Also see Command 129. The HART I/O module has a fixed
setting where 1 = single transmitter, unknown (single unknown) short
addresses of 0 to 15. There are no request data bytes.
Table B.23 Command 149 Request and Response Data Bytes
Byte
Description
Value
Request Data Bytes
0
SCAN_EN
General scan enable/disable
0 = All scanning
disabled
1 = Normal scan
enabled
2 = Special scan
enabled
Response Data Bytes
0
SCAN_EN
Scan enable/disable
0 = All scanning
disabled
1 = Normal scan
enabled
2 = Special scan
enabled
Command-specific Response Codes
2
Error
Invalid selection
5
Error
Too few data bytes received
16
Error
Access restricted
32
Error Busy
Table B.24 Command 152 Response Data Bytes
Byte
Description
Value
Response Data Bytes
0
LOC_MET
Locate method
0 = Single analog
Command-specific Response Codes
16
Error
Access restricted
32
Error Busy