Analog fault state fault mode local fault mode – Rockwell Automation 1797-OE8H FLEX Ex HART Analog Modules User Manual User Manual
Page 168
Publication 1797-6.5.3 - March 2006
D-4 Configure the 1797-OE8H Module in RSLogix 5000 Software Over the ControlNet Network
Analog Fault State
Fault Mode
Local Fault Mode
The Local Fault mode uses bit [Adapter Name]:[Slot]:C.Data[0].15.
Analog Fault State Value for
Channel
Bits
0 [Adapter
Name]:[Slot]:C.Data[3]
1
[Adapter Name]:[Slot]:C.Data[4]
2
[Adapter Name]:[Slot]:C.Data[5]
3
[Adapter Name]:[Slot]:C.Data[6]
4
[Adapter Name]:[Slot]:C.Data[7]
5
[Adapter Name]:[Slot]:C.Data[8]
6
[Adapter Name]:[Slot]:C.Data[9]
7
[Adapter Name]:[Slot]:C.Data[10]
Bits 9 or 11
Bits 8 or 10
Min Value of Data Range
0
0
Max Value of Data Range
0
1
Hold Last State
1
0
Analog Fault State Value
1
1
Channel
Bits
0 and 1
[Adapter Name]:[Slot]:C.Data[0].12
2 and 3
[Adapter Name]:[Slot]:C.Data[0].13
4 and 5
[Adapter Name]:[Slot]:C.Data[1].12
6 and 7
[Adapter Name]:[Slot]:C.Data[1].13
Disabled
0
Enabled
1
Communications Fault
0
Any Fault
1