beautypg.com

Data format alarm example, Overrange alarm, Underrange alarm – Rockwell Automation 1797-OE8H FLEX Ex HART Analog Modules User Manual User Manual

Page 18

background image

Publication 1797-6.5.3 - March 2006

1-4 About the FLEX Ex HART Analog Modules

Data Format Alarm Example

In this example, the normal active data range is 4 to 20 mA. The alarms are
generated in three overlapping bands.

Overrange Alarm

The Overrange alarm notifies you when module input is overrange. When the
input signal exceeds 100% (20 mA), an Overrange Alarm is generated.

This alarm stays active at any value above 100% of range and is always enabled
by the module.

Underrange Alarm

The Underrange alarm works in a fashion converse to the overrange. This
feature notifies you when the input signal falls underrange. If the input signal
falls below 0% (4 mA), an Underrange Alarm is generated.

This alarm stays active at any value below 0% of range and is always enabled by
the module.

PHYSICAL INPUT SIGNAL RANGE

0 mA

4 mA

20 mA

22 mA

Remote Fault

Remote Fault

Local
Fault

Local
Fault

Underrange

Overrange

Programmable

in 20 0.1 mA

Steps by Error

Level 0.1 mA

Steps

Parameter

-12.50%

0.00%

-25.00%

Remote Transmitter Error

Up/Down Parameter

Determines Which of These

is Active

Programmable

in 20 0.1 mA

Steps by Error

Level 0.1 mA

Steps

Parameter

100.00%

112.50%

41666

This manual is related to the following products: