beautypg.com

Rockwell Automation 1797-OE8H FLEX Ex HART Analog Modules User Manual User Manual

Page 50

background image

Publication 1797-6.5.3 - March 2006

2-20 Understand Configurable FLEX Ex Analog Module Features

Secondary Master Enable (SME) and Primary Master Inhibit (PMI)

These two bits control a few module internal functions individually for
channels 0 to 7.

HART Status LEDs

When this bit is set, the LEDs are used for HART diagnostics. LED behavior
changes to show communication on HART with each LED representing a
HART loop. A flashing yellow LED indicates that communication is currently
being processed while a solid yellow LED means that this device is in the
transmitter list.

HART Status Inhibit

When this bit is set, the HART communication status is not shown in the
realtime data table to enable compatibility. The appropriate areas are cleared
with zeroes.

50/60 Hz Filter

The values are:

• 0 = 50 Hz (default)
• 1 = 60 Hz

Table 2.18

Bits

(1)

1 (Default)

2

3

4

PMI

8, 9, 10, 11, 12, 13, 14, 15

0

0

1

1

SME

0, 1, 2, 3, 4, 5, 6, 7

0

1

0

1

HART Smooth Filter Pulsed

On

Off

On

Rebuild On

On

Off

Off

HART Read Back On

On

Off

Off

Primary Master On

On

Off

Off

Secondary Master Off

On

Off

On

1 Where:

Ch0 - bits 0 and 8; Ch1 - bits 1 and 9; Ch2 - bits 2 and 10; Ch3 - bits 3 and 11;
Ch4 - bits 4 and 12; Ch5 - bits 5 and 13; Ch6 - bits 6 and 14; Ch7 - bits 7 and 15

This manual is related to the following products: