Rockwell Automation 1797-OE8H FLEX Ex HART Analog Modules User Manual User Manual
Page 50
Publication 1797-6.5.3 - March 2006
2-20 Understand Configurable FLEX Ex Analog Module Features
Secondary Master Enable (SME) and Primary Master Inhibit (PMI)
These two bits control a few module internal functions individually for
channels 0 to 7.
HART Status LEDs
When this bit is set, the LEDs are used for HART diagnostics. LED behavior
changes to show communication on HART with each LED representing a
HART loop. A flashing yellow LED indicates that communication is currently
being processed while a solid yellow LED means that this device is in the
transmitter list.
HART Status Inhibit
When this bit is set, the HART communication status is not shown in the
realtime data table to enable compatibility. The appropriate areas are cleared
with zeroes.
50/60 Hz Filter
The values are:
• 0 = 50 Hz (default)
• 1 = 60 Hz
Table 2.18
Bits
(1)
1 (Default)
2
3
4
PMI
8, 9, 10, 11, 12, 13, 14, 15
0
0
1
1
SME
0, 1, 2, 3, 4, 5, 6, 7
0
1
0
1
HART Smooth Filter Pulsed
On
Off
On
Rebuild On
On
Off
Off
HART Read Back On
On
Off
Off
Primary Master On
On
Off
Off
Secondary Master Off
On
Off
On
1 Where:
Ch0 - bits 0 and 8; Ch1 - bits 1 and 9; Ch2 - bits 2 and 10; Ch3 - bits 3 and 11;
Ch4 - bits 4 and 12; Ch5 - bits 5 and 13; Ch6 - bits 6 and 14; Ch7 - bits 7 and 15