B-20 FLEX Ex HART Module Commands

Command 147

Command 147 is the Write Normal SCAN command.

Command 148

Use the Read SCAN Status command to specify the status of the SCAN
function. Where 0 = SCAN function disabled (default after you cycle power);
1 = normal SCAN function activated; and 2 = special SCAN function
activated (see Command 158 and Command 159). There are no request data
bytes.

Table B.21 Command 147 Request and Response Data Bytes

Byte

Description

Value

Request Data Bytes

0

SCAN_CMD

Scan command

1 = Command 1
2 = Command 2
3 = Command 3

Response Data Bytes

0

SCAN_CMD

Scan command

1 = Command 1
2 = Command 2
3 = Command 3

Command-specific Response Codes

2

Error

Invalid selection

5

Error

Too few data bytes received

16

Error

Access restricted

32

Error Busy

Table B.22 Command 148 Response Data Bytes

Byte

Description

Value

Response Data Bytes

0

SCAN_EN

General scan status

0 = All scanning
disabled
1 = Normal scan
enabled
2 = Special scan
enabled

Command-specific Response Codes

16

Error

Access restricted

32

Error Busy