Assigning power supplies -8, Assigning power supplies – Rockwell Automation 1797-OE8H FLEX Ex HART Analog Modules User Manual User Manual
Page 106
Publication 1797-6.5.3 - March 2006
6-8 Apply FLEX Ex Analog I/O Modules
Assigning Power Supplies
Note the amount of power each module requires and assign it to a power
supply output. Continue to assign modules to the power supply output until
the supply’s output power rating is consumed. The graphic below shows the
number of modules per power supply output.
Each power supply output in the FLEX Ex system is rated for 8.5 W.
Modules can be attached to the output until their combined power equals
that number. Do not exceed the power supply maximum of 8.5 W.
Modules
0
5
3
2
1
4
IRT8
1.6W
IRT8
1.6W
IRT8
1.6W
IRT8
1.6W
IRT8
1.6W
IRT8
1.6W
IRT8
1.6W
IRT8
1.6W
IRT8
1.6W
IRT8
1.6W
IRT8
1.6W
IRT8
1.6W
41661
IBN16
2.8W
IBN16
2.8W
IBN16
2.8W
IBN16
2.8W
IBN16
2.8W
IBN16
2.8W
IBN16
2.8W
IJ2
4.25W
IJ2
4.25W
IJ2
4.25W
IJ2
4.25W
OE8H
6.3W
IE8H
7.5W
ACNR
8.5W
RPFM
(In
RPFM
(In
RPA
8.5W
Modules Per Power Supply Output