Command 134 – Rockwell Automation 1797-OE8H FLEX Ex HART Analog Modules User Manual User Manual
Page 133
Publication 1797-6.5.3 - March 2006
FLEX Ex HART Module Commands B-9
Command 134
The Read Scan List command returns the extended addresses of the
transmitters. No more than 49 instruments will be returned. If the index is too
large, no list is generated and only the index is present in the reply.
7…11
EXT_ADDR_I
Extended address of instrument I
—
12
COUNT_I
Bytes before next item
13
ERROR_I
Error I
Table B.9 Command 134 Request and Response Bytes
Byte
Description
Value
Request Data Bytes
0…1
INDEX
Instrument scan list index
—
Response Data Bytes
0
INDEX
Instrument scan list index
—
2…6
EXT_ADDR_0
Extended address of first instrument
7…11
EXT_ADDR_I
Extended address of instrument I
Command-specific Response Codes
5
Error
Too few data bytes received
16
Error
Access restricted
32
Error
Busy
Table B.8 Command 133 Request and Response Data Bytes
Byte
Description
Value