Select protection method(s), Match field devices and i/o modules – Rockwell Automation 1797-OE8H FLEX Ex HART Analog Modules User Manual User Manual
Page 101
Publication 1797-6.5.3 - March 2006
Apply FLEX Ex Analog I/O Modules 6-3
Select Protection
Method(s)
Although the FLEX Ex system primarily uses the Intrinsic Safety protection
method, the system uses all methods listed below.
Match Field Devices and
I/O Modules
You must match field devices and I/O modules for your application to
function properly. Consider the following:
• Verify field device and I/O module operational characteristics
• Match entity parameters of field devices and I/O modules
P/I Analog Transmitter Functional and IS Parameters
The figure below shows a typical pressure to current analog transmitter. Two
types of characteristics are shown, functional and IS.
Table 6.1 Protection Methods for Hazardous Applications
Protection Method
Designation
1(1)
(1)
In the Non-Incendive protection method, n: used locally in the United States and United Kingdom.
In the Intrinsic Safety method, ia: Zone 0, 1, 2 & ib: Zone 1, 2.
Method of Achieving
Protection
Intrinsic Safety
EEx
ia
/EEx
ib
Energy Limiting
Encapsulation
EEx
m
Segregation
Increased Safety
EEx
e
Refined Mechanical Design
Flameproof
EEx
d
Containment
IMPORTANT
As not all protection methods are applicable for all
locations, consult local certifying agencies to
determine acceptable protection methods for your
application.
600
250
14 16.4
24.7
42
4 to 20 mA IS
P/I Transmitter
14 to 42V operate
EEx ia IIC T4
Ui = 30V
Ii = 165 mA
Ci = 22.5 nF
Li = 730 uH
Power Supply Voltage
External
Load
Resistance
41662