1797-oe8h output module, Specifications – Rockwell Automation 1797-OE8H FLEX Ex HART Analog Modules User Manual User Manual
Page 122
Publication 1797-6.5.3 - March 2006
A-10 Specifications
1797-OE8H Output Module
Specifications
Number of Outputs
8 single-ended, non-isolated
Outputs
Type of Protection
EEx ia IIB/IIC T4
Module
Type of Protection
EEx ib IIB/IIC T4
Resolution
13 bits
Transfer Characteristics
Accuracy at 20 °C (68 °F)
Temperature Drift
0.1% of output signal range
0.010%/C of output signal range
Load Range
Current
Voltage Available at 22 mA
Load
0…22 mA
> 15V
0…680
Ω @ 22 mA, 0…770 Ω @ 20 mA
Data Format
Configurable
Step Response to 99% of FS
115 ms (in HART mode)
18 ms (in standard mode)
Module from Adapter
Best/Worst Update Time
200 ms/1600 µs
Indicators
8 red fault indicators
1 green power
8 yellow HART comm indicators
Output Ch 0…Ch 7
(Intrinsically Safe)
(Terminals: 0…1; 4…5;
8…9; 12…13; 17…18;
21…22; 25…26; 29…30)
U
O
< 21.6V
I
O
< 92 mA
P
O
< 500 mW
Isolation Path
Output to Power Supply
Output to FLEXBus
Output to Output
Power Supply to FLEXBus
Isolation Type
Galvanic to DIN EN50020
Galvanic to DIN EN50020
None
Galvanic to DIN EN50020
Power Supply
(+V, -V Intrinsically Safe)
(Terminals: 34/50 (+);
35/51 (-))
U
i
< 9.5V dc
I
i
< 1 A
L
i
= Negligible
C
i
= 120 nF
Module Field-Side Power
Consumption
6.1 W
Power Dissipation
5.4 W
Thermal Dissipation
20.8 BTU/hr
Module Location
Cat. No. 1797-TB3 or -TB3S Terminal Base Unit
Conductors Wire Size
12 gauge (4mm
2
) stranded maximum
1.2 mm (3/64 in) insulation maximum
Dimensions
46 x 94 x 75 mm (1.8 x 3.7 x 2.95 in)
Weight 200
g
(approximately)