beautypg.com

1797-oe8h output module, Specifications – Rockwell Automation 1797-OE8H FLEX Ex HART Analog Modules User Manual User Manual

Page 122

background image

Publication 1797-6.5.3 - March 2006

A-10 Specifications

1797-OE8H Output Module

Specifications

Number of Outputs

8 single-ended, non-isolated

Outputs

Type of Protection

EEx ia IIB/IIC T4

Module

Type of Protection

EEx ib IIB/IIC T4

Resolution

13 bits

Transfer Characteristics

Accuracy at 20 °C (68 °F)
Temperature Drift

0.1% of output signal range
0.010%/C of output signal range

Load Range

Current
Voltage Available at 22 mA
Load

0…22 mA
> 15V
0…680

Ω @ 22 mA, 0…770 Ω @ 20 mA

Data Format

Configurable

Step Response to 99% of FS

115 ms (in HART mode)
18 ms (in standard mode)

Module from Adapter
Best/Worst Update Time

200 ms/1600 µs

Indicators

8 red fault indicators
1 green power
8 yellow HART comm indicators

Output Ch 0…Ch 7
(Intrinsically Safe)

(Terminals: 0…1; 4…5;
8…9; 12…13; 17…18;
21…22; 25…26; 29…30)

U

O

< 21.6V

I

O

< 92 mA

P

O

< 500 mW

Isolation Path

Output to Power Supply
Output to FLEXBus
Output to Output
Power Supply to FLEXBus

Isolation Type
Galvanic to DIN EN50020
Galvanic to DIN EN50020
None
Galvanic to DIN EN50020

Power Supply
(+V, -V Intrinsically Safe)

(Terminals: 34/50 (+);
35/51 (-))

U

i

< 9.5V dc

I

i

< 1 A

L

i

= Negligible

C

i

= 120 nF

Module Field-Side Power
Consumption

6.1 W

Power Dissipation

5.4 W

Thermal Dissipation

20.8 BTU/hr

Module Location

Cat. No. 1797-TB3 or -TB3S Terminal Base Unit

Conductors Wire Size

12 gauge (4mm

2

) stranded maximum

1.2 mm (3/64 in) insulation maximum

Dimensions

46 x 94 x 75 mm (1.8 x 3.7 x 2.95 in)

Weight 200

g

(approximately)

This manual is related to the following products: