B-12 FLEX Ex HART Module Commands
Command 137
For the given long frame addresses, the Write SCAN Status of the Transmitters
command sets the SCAN status of the transmitters (0 = disable SCAN, 1 =
enable SCAN). No more than 31 instruments may be requested.
Command-specific Response Codes
5
Error
Too few data bytes received
16
Error
Access restricted
17
Error
Too many items requested
32
Error Busy
Table B.12 Command 137 Request and Response Data Bytes
Byte
Description
Value
Request Data Bytes
0…4
EXT_ADDR_0
Extended address of instrument 0
—
5
COUNT_0
Bytes before next item
6
SCAN_0
Scan enable/disable on instrument 0
0 = Scan disable
1 = Scan enable
…
EXT_ADDR_I
Extended address of instrument I
—
…
COUNT_I
Bytes before next item
…
SCAN_I
Scan enable/disable on instrument I
…
…
…
Response Data Bytes
0…4
EXT_ADDR_0
Extended address of instrument 0
—
5
COUNT_0
Bytes before next item
6
ERROR_0
Error 0
0 = No error.
31 = The scan
value sent is
identical to the
current one.
64 = Unknown
instrument. No
data is included
for that
instrument.
65 = Scan value
not allowed. No
data included for
that instrument.
Table B.11 Command 136 Request and Response Bytes
Byte
Description
Value