Rockwell Automation 1797-OE8H FLEX Ex HART Analog Modules User Manual User Manual
Page 91
Publication 1797-6.5.3 - March 2006
Calibrate Your Module 5-15
Table 5.10 1797-OE8H Interpretation of Command Data Structure Content During Write Access
Command Byte
Item Byte
Data1 Byte
Data2 Byte
Reserved (Binary)
Command Bits 0…5 (Decimal)
10
(1)
1
Calibration command min scale
Channel-Mask
Reserved
(4)
Reserved
2
Calibration command max scale
3
Write measured min scale value (Current, uA)
Value
low-byte
Value
high-byte
4
Write measured min scale value (Voltage, uV)
5
Write measured max scale value (Current, uA)
6
Write measured max scale value (Voltage, uV)
7
Reserved
(2)
—
—
—
8
Set all calibration values to default
Reserved
Reserved
Reserved
9
Set one specified calibration value to default
Value identifier (0)
10
Reserved
(3)
Reserved
Reserved
Reserved
11
Reserved
12
Reserved
13
Reserved
14
Save calibration data to EEPROM
Reserved
Reserved
Reserved
15…63 Reserved
—
—
—
(1)
Always must be 10
bin
.
(2)
Do not use. Designated for future use.
(3)
Reserved. Used during manufacture of the product. Do not use.
(4)
In attempt to write this byte, write 0.