6-10 Apply FLEX Ex Analog I/O Modules

Power Supply Considerations

When applying power, consider the certain characteristics of the wire
connecting the power supply output to a module’s power input. The wire
cannot exhibit more than:

• 0.1 Ω of resistance (+V and -V combined)
• 800 nF of capacitance
• 10 µF of inductance

Typically, these restrictions will yield wiring lengths of not more than 3.5 m or
5.8 m (1.5 mm

2

and 2.5 mm

2

wire respectively) without the use of special

wiring or wiring methods.

Chapter Summary

In this chapter you learned how to apply the FLEX Ex analog I/O modules.
Move to Chapter 7 to learn about troubleshooting your modules.