Rack Mounting Procedure (6185-N)

1. Carefully remove the monitor from its packaging.

2. Locate holes in the cabinet front mounting rails corresponding to the

holes in the monitor front panel. Install clip nuts behind the holes in
the rails if threaded rails are not provided.

Note:

The mounting rails that run vertically along the inside
edges of the front opening of an EIA rack cabinet can
be of two types:
• “Wide” rails have holes spaced 0.5"(12.7 mm) and

1.25"(31.8 mm) on centers, in a repeating pattern.
Wide rails are prevalent in Europe.

• “Universal” rails have holes spaced 0.5"(12.7 mm),

0.625"(31.8 mm), and 0.625"(31.8 mm) on centers,
in a repeating pattern. Thus, the universal rails have
a hole pattern that contains the wide pattern but
provides an additional hole at the midpoint of the
pattern. Universal rails are most prevalent in the US.

3. Install the monitor into the cabinet from the front.

4. Secure the monitor chassis to the cabinet by installing panel-

mounting screws through the holes in the monitor front panel and
into the rails behind.