Bulletin 284 Programmable Parameters for Sensorless Vector Controllers
Starter Protection Group
Breaker Type
This parameter identifies the Bulletin 140M used in this product.
0 = 140M-D8N-C10
1 = 140M-D8N-C25
Parameter Number
22
Access Rule
GET
Data Type
BOOL
Group
Starter Protection
Units
—
Minimum Value
0
Maximum Value
1
Default Value
—
PrFlt Reset Mode
This parameter is the Protection Fault reset mode.
0 = Manual
1 = Automatic
Parameter Number
23
Access Rule
GET/SET
Data Type
BOOL
Group
Starter Protection
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
Pr Fault Enable
This parameter enables the Protection Fault by setting the bit to 1.
Parameter Number
24
Access Rule
GET/SET
Data Type
WORD
Group
Starter Protection
Units
—
Minimum Value
0
Maximum Value
65535
Default Value
64927
Bit
Function
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
X
Short Circuit
—
—
—
—
—
—
—
—
—
—
—
—
—
—
X
—
Overload
—
—
—
—
—
—
—
—
—
—
—
—
—
X
—
—
Phase Short
—
—
—
—
—
—
—
—
—
—
—
—
X
—
—
—
Ground Fault
—
—
—
—
—
—
—
—
—
—
—
X
—
—
—
—
Stall
—
—
—
—
—
—
—
—
—
—
X
—
—
—
—
—
Control Power
—
—
—
—
—
—
—
—
—
X
—
—
—
—
—
—
IO Fault
—
—
—
—
—
—
—
—
X
—
—
—
—
—
—
—
Overtemperature
—
—
—
—
—
—
—
X
—
—
—
—
—
—
—
—
Over Current
—
—
—
—
—
—
X
—
—
—
—
—
—
—
—
—
Dnet Power Loss
—
—
—
—
—
X
—
—
—
—
—
—
—
—
—
—
Internal Comm
—
—
—
—
X
—
—
—
—
—
—
—
—
—
—
—
DC Bus Fault
—
—
—
X
—
—
—
—
—
—
—
—
—
—
—
—
EEprom
—
—
X
—
—
—
—
—
—
—
—
—
—
—
—
—
HW Fault
—
X
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Restart Retries
X
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Misc. Fault