DeviceNet™ Commissioning
6-7
Using Automap feature with
default Input and Output (I/O)
Assemblies
The Automap feature available in all Rockwell Automation scanners
will automatically map the information as shown below. If manual
mapping is not required, the information below can be used to map a
device based on the default configuration.
Table 6.1
Default Input and Output (I/O) Assemblies
Default Input and Output (I/O)
Assembly Formats
The I/O assembly format for the ArmorStart is identified by the value
in parameter 11 (Consumed IO Assy.) and parameter 12 (Produced IO
Assy.). These values determine the amount and arrangement of the
information communicated to the master scanner. The tables below
identify the default information produced and consumed by the
standard starter. For additional formats and advance configurations
please reference Table B.11 on page B-5.
Table 6.2
Instance 160 — Default Consumed Data for Standard Distributed
Motor Controller (1 byte)
Table 6.3
Instance 161 — Default Produced Data for Standard Distributed
Motor Controller (2 bytes)
Default
Message type
Polled
Consumed data size
1 byte (Rx)
Produced data size
2 bytes (Tx)
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
User Out B
User Out A
Not Used
Not Used
Not Used
Fault Reset
Run Rev
Run Fwd
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Not Used
Not Used
Not Used
Ready
Running Rev
Running Fwd
Warning
Tripped
1
Not Used
Not Used
140M On
HOA
Status
User In 3
User In 2
User In 1
User In 0