Rockwell Automation 284D ArmorStart - Safety Version - User Manual User Manual
Page 228
B-8
Bulletin 280/281 CIP Information
Table B.22 Instance 160 is the default output (consumed) assembly for
Standard Distributed Motor Controllers
Table B.23 Instance 162 is the standard output (consumed) assembly with
Network Inputs
Standard Distributed Motor Controller Input (Produced)
Assemblies
Table B.24 Instance 52 is the required input (produced) assembly defined in
the DeviceNet Motor Starter Profile
Table B.25 Instance 161 is the default input (produced) assembly for
Standard Distributed Motor Controllers
Instance 160 — Default Consumed Standard Distributed Motor Controller
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
User Out
B
User Out
A
—
—
—
Fault
Reset
Run Rev Run Fwd
Instance 162 — Standard Consumed Starter with Network Inputs
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
User Out
B
User Out
A
—
—
—
Fault
Reset
Run Rev Run Fwd
1
Net In 8
Net In 7
Net In 6
Net In 5
Net In 4
Net In 3
Net In 2
Net In 1
2
Net In 16 Net In 15 Net In 14 Net In 13 Net In 12 Net In 11 Net In 10 Net In 9
Instance 52 — ODVA Starter
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
—
—
—
—
—
—
Running
—
Fault
Instance 161 — Default Producted Standard Distributed Motor Controller
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
—
—
—
Ready
Running
Rev
Running
Fwd
Warning
Tripped
1
—
—
140M On
HOA
Stat.
User In 3 User In 2 User In 1 User In 0