Bulletin 284 Programmable Parameters for Sensorless Vector Controllers
4-37
Accel Time 2
When active, sets the rate of acceleration for all speed increases except for jog.
Parameter Number
167
Related Parameters
139, 151, 152, 153, 154,
170…173, 174…177,
240…247
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
0.1 sec
Minimum Value
0.0
Maximum Value
600.0
Default Value
20.0
Decel Time 2
When active, sets the rate of deceleration for all speed decreases except for jog.
Parameter Number
168
Related Parameters
140, 151, 152, 153, 154,
170…173, 174…177,
240…247
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
0.1 sec
Minimum Value
0.0
Maximum Value
600.0
Default Value
20.0
Internal Freq
Provide the frequency command to drive when Parameter 138 (Speed Reference) is
set to 1 Internal Freq. When enabled, this parameter will change the frequency
command in real time.
Parameter Number
169
Related Parameters
138, 162
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
0.1 Hz
Minimum Value
0.0
Maximum Value
400.0
Default Value
60.0
Maximum Freq
Accel Time
--------------------------------------
Accel Rate
=
Parameter 135
(Maximum Freq)
Speed
Param.
139 or
167
(Accel
Time x)
0
0
Time
Param.
140 or
168
(Decel
Time x)
Acceleration
Deceleration
Maximum Freq
Decel Time
--------------------------------------
Decel Rate
=
Parameter 135
(Maximum Freq)
Speed
Param.
139 or
167
(Accel
Time x)
0
0
Time
Param.
140 or
168
(Decel
Time x)
Acceleration
Deceleration