Bulletin 284 Programmable Parameters for Sensorless Vector Controllers
4-45
Clear a Type 1 Fault and Restart the Drive
1. Set Parameter 192 (Auto Rstrt Tries) to a value other than 0.
2. Set Parameter 193 (AutoRstrt Delay) to a value other than 0.
Clear an Overvoltage, Undervoltage, or Heatsink OvrTmp Fault
without Restarting the Drive
1. Set Parameter 192 (Auto Rstrt Tries) to a value other than 0.
2. Set Parameter 193 (AutoRstrt Delay) to 0.
Auto Rstrt Tries
Set the maximum number of times the drive attempts to reset a fault and restart.
Parameter Number
192
Related Parameter
155, 158, 161, 193
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
1
Minimum Value
0
Maximum Value
9
Default Value
0
ATTENTION
!
Equipment damage and/or personal injury may result if this
parameter is used in an inappropriate application. Do not
use this function without considering applicable local,
national, and international codes, standards, regulations, or
industry guidelines.
Auto Rstrt Delay
Sets time between restart attempts when Parameter 192 (Auto Rstrt Tries) is set to a
value other than zero.
Parameter Number
193
Related Parameters
192
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
0.1 sec
Minimum Value
0.0
Maximum Value
300.0 sec
Default Value
1.0 sec