Appendix

A

Specifications

Bulletin 280/281

Electrical Ratings

UL/NEMA

IEC

Power Circuit

Rated Operation Voltage

380Y/220…480Y/277V AC

380Y/220…480Y/277V AC

Rate Insulation Voltage

600V

Rated Impulsed Voltage

4 kV

Dielectric Withstand

2200V AC

2500V AC

Operating Frequency

50/60 Hz

Utilization Category

N/A

AC-3

Protection Against Shock

N/A

IP2X

Rated Operating Current Max.

2.5 A

5.5 A

16 A

Control
Circuit

Rated Operation Voltage

24V DC (+10%, -15%) A2 (should be grounded at voltage source)

Rate Insulation Voltage

250V

Rated Impulsed Voltage

4 kV

Dielectric Withstand

1500V AC

2000V AC

Overvoltage Category

III

Operating Frequency

50/60 Hz

Short Circuit
Protection

SCPD Performance Type 1

Sym. Amps RMS @ 480Y/277V

Current Rating

0.5…2.5 A

65kA

1.1…5.5 A

3.2…16 A

30kA

SCPD List

Size per NEC Group Motor

Power Requirements

Units

W/O HOA

W/ HOA

Control Voltage

Volts

24V DC

24V DC

Contactor (Pick Up)

Amps

1.09

1.09

Contactor (Hold In)

Amps

0.30

0.30

Total Control Power (Pick Up)

VA (W)

(26.0 W)

(26.0 W)

Total Control Power (Hold In)

VA (W)

(7.2 W)

(7.2 W)

External Devices powered by Control Voltage

Outputs (2) 1 A max. each)

Amps

2

2

Total Control (Pick Up) with max. outputs

VA (W)

(65.0 W)

(73.0 W)

Total Control (Hold In) with max. outputs

VA (W)

(50.0 W)

(58.0 W)

Input Ratings

Rated Operation Voltage

24V DC

Input On-State Voltage Range

10…26V DC

Input On-state Current

3.0 mA @ 10V DC

7.2 mA @ 24V DC

Input Off-state Voltage Range

0…5V DC

Input Off-state Current

<1.5 mA

Input Filter — Software Selectable

Off to On

Settable from 0…64 ms in 1 ms increments

On to Off

Settable from 0…64 ms in 1 ms increments

Input Compatibility

N/A

IEC 1+

Number of inputs

4

Sensor Source

Voltage Status Only

11…25V DC from DeviceNet™

Current Available

50 mA MAX per Input, 200 mA Total

Output Ratings (Sourced
from Control Circuit)

Rated Operation Voltage

240V AC / 30V DC

240V AC / 30V DC

Rate Insulation Voltage

250V

250V

Backplane Current Load

400 mA

50/60 Hz

50/60 Hz

Type of control circuit

Electromechanical Relay

Kind of Current

AC/DC

Conventional Thermal Current I

th

Total of both outputs

2 A

Type of Contacts

Normally Open (N.O.)

Number of Contacts

2