Rockwell Automation 284D ArmorStart - Safety Version - User Manual User Manual
Page 230
![background image](/manuals/578099/230/background.png)
B-10
Bulletin 280/281 CIP Information
Connection Object — CLASS CODE
0x0005
No class attributes are supported for the Connection Object
Multiple instances of the Connection Object are supported, instances
1, 2, and 4 from the group 2 predefined master/slave connection set,
instances 5 and 6 are available through explicit UCMM connections.
Instance 1 is the Predefined Group 2 Connection Set Explicit
Message Connection. The following instance 1 attributes is
supported:
Table B.28 Connection Object Instance 1 Attributes
Attribute
ID
Access
Rule
Name
Data
Type
Value
1
Get
State
USINT
0=nonexistant
1=configuring
3=established
4=timed out
2
Get
Instance Type
USINT
0=Explicit
Message
3
Get
Transport Class Trigger
USINT
0x83 — Server,
Transport Class 3
4
Get
Produced Connection ID
UINT
10xxxxxx011
xxxxxx = node
address
5
Get
Consumed Connection ID
UINT
10xxxxxx100
xxxxxx = node
address
6
Get
Initial Comm Characteristics
USINT
0x22
7
Get
Produced Connection Size
UINT
0x61
8
Get
Consumed Connection Size
UINT
0x61
9
Get/Set
Expected Packet Rate
UINT
in ms
12
Get
Watchdog Action
USINT
01 = auto delete
03 = deferred delete
13
Get
Produced Connection Path Length
UINT
0
14
Get
Produced Connection Path
Empty
15
Get
Consumed Connection Path Length
UINT
0
16
Get
Consumed Connection Path
Empty