Bulletin 284 troubleshooting, Fault definitions – Rockwell Automation 284D ArmorStart - Safety Version - User Manual User Manual
Page 186
11-6
Troubleshooting
Bulletin 284 Troubleshooting
Fault Definitions
Some of the Bulletin 284 ArmorStart Distributed Motor Controller faults are detected by the internal hardware of
the ArmorStart, while others are detected by the internal drive. For internal drive faults, the internal hardware of the
ArmorStart simply polls the drive for the existence of faults and reports the fault state. No fault latching is done by
the internal hardware of the ArmorStart for these faults. The Pr FltReset Mode parameter (Parameter 23)
determines the Auto Resettability of only the faults that are detected on the main control board. These faults are
listed as “param 23” autoresettable in 11.7. The Auto Resettability of the faults that are detected in the internal
drive is controlled by internal drive parameters. These faults are listed as drive controlled in 11.7.The following
flowchart for Bulletin 284 units, is provided to aid in quick troubleshooting.
Faulted Display
See
Table 11.7
Fault
LED
Network
LED
Yes
No
See
Table 11.16
See
Common
Symptoms and
Corrective
Actions
Motor will not
start
Define Nature
of the Problem