Starter setup – Rockwell Automation 284D ArmorStart - Safety Version - User Manual User Manual
Page 69
Bulletin 280/281 Programmable Parameters
3-27
Starter Setup
Table 3.2
FLA Setting Ranges and Default Values (with indicated setting
precision)
% Therm Utilized
This parameter displays the
% Thermal Capacity used
Parameter Number
105
Access Rule
GET/SET
Data Type
USINT
Group
Starter Display
Units
% FLA
Minimum Value
0
Maximum Value
100
Default Value
0
FLA Setting
The motor’s full load current
rating is programmed in this
parameter
Parameter Number
106
Access Rule
GET/SET
Data Type
INT
Group
Starter Setup
Units
xx.x Amps
Minimum Value
See Table 3.2
Maximum Value
See Table 3.2
Default Value
See Table 3.2
FLA Current Range (A)
Default Value
Minimum Value
Maximum Value
0.24
1.2
0.24
0.5
2.5
0.5
1.1
5.5
1.1
3.2
16.0
3.2
Overload Class
This parameter allows the
installer to select the overload
class
1= Overload Class 10
2= Overload Class 15
3= Overload Class 20
Parameter Number
107
Access Rule
GET/SET
Data Type
USINT
Group
Starter Setup
Units
xx.x Amps
Minimum Value
1
Maximum Value
3
Default Value
1
OL Reset Level
This parameter allows the
installer select the % Thermal
Capacity which an overload can
be cleared
Parameter Number
108
Access Rule
GET/SET
Data Type
USINT
Group
Starter Setup
Units
% FLA
Minimum Value
0
Maximum Value
100
Default Value
75