beautypg.com

Rockwell Automation 284D ArmorStart - Safety Version - User Manual User Manual

Page 66

background image

3-24

Bulletin 280/281 Programmable Parameters

Zone #2 Control

Zone 2 Control Word. Default
Bit 0 and Bit 1 set, all other bits
clear.
Bit0=Security Enable 1=Enable
data security
Bit1=COS Cnxn 1=Consume
DNet Group 2 COS messages
Bit2=Poll Cnxn
1=Consume DNet Group 2 Poll
Response msgs.
Bit3=Strobe Cnxn
1=Consume DNet Group 2
Strobe Response msgs.
Bit4=Multicast Poll
1=Consume Multicast Poll
Response messages

Parameter Number

91

Access Rule

GET/SET

Data Type

BYTE

Group

ZIP Parameters

Units

MinimumValue

0

Maximum Value

255

Default Value

3

Zone #3 Control

Zone 3 Control Word. Default
Bit 0 and Bit 1 set, all other bits
clear.
Bit0=Security Enable 1=Enable
data security
Bit1=COS Cnxn 1=Consume
DNet Group 2 COS messages
Bit2=Poll Cnxn
1=Consume DNet Group 2 Poll
Response msgs.
Bit3=Strobe Cnxn
1=Consume DNet Group 2
Strobe Response msgs.
Bit4=Multicast Poll
1=Consume Multicast Poll
Response messages

Parameter Number

92

Access Rule

GET/SET

Data Type

BYTE

Group

ZIP Parameters

Units

MinimumValue

0

Maximum Value

255

Default Value

3

Zone #4 Control

Zone 3 Control Word. Default
Bit 0 and Bit 1 set, all other bits
clear.
Bit0=Security Enable 1=Enable
data security
Bit1=COS Cnxn 1=Consume
DNet Group 2 COS messages
Bit2=Poll Cnxn
1=Consume DNet Group 2 Poll
Response msgs.
Bit3=Strobe Cnxn
1=Consume DNet Group 2
Strobe Response msgs.
Bit4=Multicast Poll
1=Consume Multicast Poll
Response messages

Parameter Number

93

Access Rule

GET/SET

Data Type

BYTE

Group

ZIP Parameters

Units

MinimumValue

0

Maximum Value

255

Default Value

3