Rockwell Automation 284D ArmorStart - Safety Version - User Manual User Manual
Page 113
Bulletin 284 Programmable Parameters for Sensorless Vector Controllers
4-43
Brake Voltage
Sets the frequency where brake voltage is applied when Parameter 184 (Boost
Select) = 0 Custom V/Hz and Parameter 225 (Torque Perf Mode) = 0V/Hz.
Parameter Number
186
Related Parameters
131, 132, 134, 135, 184, 185,
187, 188, 225
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
1.1%
Minimum Value
0.0%
Maximum Value
100.0%
Default Value
25.0%
Brake Frequency
Sets the frequency where brake frequency is applied when Parameter 184 (Boost
Select) = 0 Custom V/Hz and Parameter 225 (Torque Perf Mode) = 0V/Hz.
Parameter Number
187
Related Parameters
131, 132, 134, 135, 184, 185,
186, 188, 225
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
0.1 Hz
Minimum Value
0.0 Hz
Maximum Value
400.0 Hz
Default Value
15.0 Hz
Maximum Voltage
Sets the highest voltage the drive will output.
Parameter Number
188
Related Parameters
104, 185, 186, 187
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
1V AC
Minimum Value
20V AC
Maximum Value
Drive Rated Volts
Default Value
Drive Rated Volts
Current Limit 1
Maximum output current allowed before current limiting occurs
Parameter Number
189
Related Parameters
133, 218
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
0.1 A
Minimum Value
0.1 A
Maximum Value
Drive rated amps X 1.8
Default Value
Drive rated amps X 1.5