beautypg.com

Safe limited speed parameter list – Rockwell Automation 21G PowerFlex 750-Series AC Drives Reference Manual User Manual

Page 78

background image

78

Rockwell Automation Publication 750-RM001F-EN-P - February 2012

Chapter 7

Safe Limited Speed (SLS) Modes

Safe Limited Speed
Parameter List

To configure the safety option for Safe Limited Speed monitoring, set these
parameters in addition to the Safe Stop parameters listed beginning on

page 69

.

Fil

e

Gr

oup

No.

Display Name
Full Name
Description

Values

Re

ad

-Write

Da

ta

T

yp

e

HOST GROUPS

Gene

ral

21

Safety Mode
Safety Mode
Defines the primary operating mode of the speed monitoring safety functions.

Setting:

3 = “Lim Speed”

RW 8-bit

Integer

Limit

ed S

peed

52

Lim Speed Input
Limited Speed Input
Configuration for Safe Limited Speed input (SLS_In).
“2NC” (1) – Dual-channel equivalent
“2NC 3s” (2) – Dual-channel equivalent 3 s
“1NC+1NO” (3) – Dual-channel complementary
“1NC+1NO 3s” (4) – Dual-channel complementary 3 s
“2 OSSD 3s” (5) – Dual-channel SS equivalent 3 s
“1NC” (6) – Single channel equivalent

Default:
Options:

0 = “Not used”

(2)

0 = “Not used”
1 = “2NC”
2 = “2NC 3s”
3 = “1NC+1NO”
4 = “1NC+1NO 3s”
5 = “2 OSSD 3s”
6 = “1NC”

RW 8-bit

Integer

53

LimSpd Mon Delay
Limited Speed Monitoring Delay
Defines the Safe Limited Speed Monitoring Delay between the SLS_In ON to OFF
transition and the initiation of the Safe Limited Speed (SLS) or Safe Maximum Speed
(SMS) monitoring.

Units:
Default:
Min/Max:

Secs
0
0 / 6553.5

RW 16-bit

Integer

55

Safe Speed Limit
Safe Speed Limit
Defines the speed limit that will be monitored in Safe Limited Speed (SLS) mode.
Units are based on rotary or linear configuration defined by P29 [Fbk 1 Units].

Units:

Default:
Min/Max:

RPM
mm/s
0
0 / 6553.5 RPM
0 / 6553.5 mm/s

RW 16-bit

Integer

Gen

eral

73

SLS Out Mode
Defines whether the SLS_Out output is pulse-tested.

(1)

If pulse-testing is turned off for any output, the SIL, Category, and PL rating is reduced
for the entire safety system.

Default:
Options:

0 = “Pulse test”
0 = “Pulse test”
1 = “No pulse test”

RW 8-bit

Integer

(1) If pulse-testing is turned off for any output, the SIL, Category, and PL rating is reduced for the entire safety system.
(2) You must configure this parameter with a non-zero value in this mode.